6ES7331-7TF01-0AB0

SKU: 6ES7331-7TF01-0AB0

BRAND: Siemens


🚚
Delivery time: 2-5 working days for South Africa
In stock - Ready for immediate dispatch
Free shipping for orders over R1,000.00
SIMATIC DP, HART Analog Input SM 331, 8 AI, 0/4 - 20mA HART, for ET200M

Analog Input Module with HART

Specifications

Supply voltage

  • Load voltage L+
  • Rated value (DC) : 24 V
  • Reverse polarity protection : Yes

Input current

  • from load voltage L+ (without load), max. : 20 mA
  • from backplane bus 5 V DC, max. : 120 mA

Output voltage

  • Power supply to the transmitters
    • present : Yes
    • Rated value (DC) : 24 V
    • short-circuit proof : Yes

Power losses

  • Power loss, typ. : 1.5 W

Analog inputs

  • Number of analog inputs : 8
  • permissible input current for current input (destruction limit), max. : 40 mA

Input ranges

  • Voltage : No
  • Current : Yes
  • Thermocouple : No
  • Resistance thermometer : No
  • Resistance : No

Input ranges (rated values), currents

  • 0 to 20 mA : Yes
  • Input resistance (0 to 20 mA) : 240 Ω
  • Input resistance (-20 to +20 mA) : 240 Ω
  • Input resistance (4 to 20 mA) : 240 Ω

Cable length

  • Cable length, shielded, max. : 800 m

Analog value creation

  • Measurement principle : Sigma Delta

Integrations and conversion time/ resolution per channel

  • Resolution with overrange (bit including sign), max. : 16 bit
  • Integration time, parameterizable : Yes
  • Integration time, ms : 20 ms@50 Hz/16.6 ms@60 Hz/100 ms@100 Hz
  • Basic conversion time, including integration time, ms : 65ms@50Hz / 55ms@60Hz / 305ms@100Hz

Encoder

  • Connection of signal encoders
    • for current measurement as 2-wire transducer : Yes
    • for current measurement as 4-wire transducer : Yes

Errors/accuracies

  • Linearity error (relative to input area) : +/- 0.01 %
  • Temperature error (relative to input area) : +/- 0.001 %/K
  • Crosstalk between the inputs, min. : 70 dB
  • Repeat accuracy in settled status at 25 °C (relative to input area) : +/- 0.1 %

Operational limit in overall temperature range

  • Current, relative to input area : +/- 0,15 %

Basic error limit (operational limit at 25 °C)

  • Current, relative to input area : +/- 0,1 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min. : 40 dB
  • Common mode interference, min. : 100 dB

Isochronous mode

  • Isochronous operation (application synchronized up to terminal) : No

Downloads

Additional Information

Device Analog Input
Type HART | ET200M
Enhance your automation with the 6ES7331-7TF01-0AB0 HART Analog Input Module. This reliable module supports 8 analog inputs, delivering precise current measurements (0/4-20mA) for optimal performance in your ET200M system. Experience superior accuracy and efficiency while ensuring easy integration and robust protection features. Ideal for industrial applications, it promises seamless operation and exceptional value.