Mecer Online UPS 10000VA 9KW, Power Factor:PF0.9, 16x12V9ah Batteries, SNMP Card, 40Hz~70Hz, Output:230Vac(±1%) 45A, Output Overload: 105%-125%, Load Transfer to Bypass Mode AfteR10min (0-30℃) OR 1min (30-40℃), 248x500x616mm, 62.1kg
10000VA 9KW Online UPS
Feature
- Higher power density, more power output
- Wider input range, higher efficiency
- Ultra low noise, multiple configurable options
- High quality LCD with wide view
Specifications
- Model : ME-10000-WPTV
- Dimensions W*D*H(mm) : 248 x 500 x616
- Weight(kg) : 62.1
Power
- Apparent Power(KVA) : 10KVA/
- Active power(KW) : 9KW
Mains
- Voltage range : 120Vac-275Vac(phase to phase)
- Current* : 52.6 A max
- Frequency range : 40Hz-70Hz
- Power factor : 0.99
Output
- Rating Voltage : 230Vac(±1%)
- Rating Current : 45A
- Frequency range : 50Hz x (1±1%); Follow main power in phase lock range
- Power factor : 0.9
Output Overload
- 105%-125%, load transfer to bypass mode after 10 min (0-30°C) or
- 1min(30-40°C);
- 125%-150%,load transfer to bypass mode after 30s;
- Over 150%, load transfer to bypass after 0.5s
- Load crest ratio : 3:1( max)
- THD : <2%( 100% Line load)
Enviromental and safety
- EMC Standard : EN IEC 62040-2:2018 / EN 62040-2:2006 / IEC 62040-2:2016
- Safety Standard : EN62040-1:2008+A1:2013
- Operation temperature : 0-40 °C
- Store temperature : -25°C to 55 °C
- Relative humidity : 20% to 90%
- Altitude : <1000m
- *The max current is under 176Vac input, full rating load and empty battery charging.
Downloads
Additional Information
| Device |
UPS |
| Type |
10000VA | 9KW | Online |